TA-Modulator
Pressure independent balancing and control valve for modulating control
The uniquely shaped EQM characteristics provide highly precise temperature control. The valve is compatible with linear, proportional or 3-point actuators. A built-in differential pressure controller provides high control authority, control stability and automatic limitation of design flow. Measurement of flow and available pressure enables system optimisation and diagnostics.
Features and Benefits
Precise temperature control
Provide uniquely shaped EQM characteristic for best modulating control.
Precise control
Uniquely shaped EQM characteristic provides an up to 6 times larger operating stroke than linear valves.
Quick hydronic balancing
Automatic flow limitation when actuator is fully open protects entire system against overflows.
Easy troubleshooting
Flow and differential pressure measuring helps to reduce pump consumption and provides all necessary data for system diagnostics.
Applications
Heating and cooling systems.
Functions
Control EQM: DN 15 low flow, DN 10-200 normal flow
Control LIN: DN 65-200 high flow
Differential pressure control
Isolation (for use during system maintenance – see "Leakage rate")
Measuring (ΔH, t, q)
Pre-setting (max. flow)
Media
Water or neutral fluids, water-glycol mixtures (0-57%).
Actuators
*) Adapter to be ordered separately, see "Adapters for actuators".
DN 100-125 HF: TA-Slider 750 ΔpV ≤ 4 bar, TA-Slider 1600 ΔpV ≤ 8 bar.
DN 10-20: TA-Slider 160, EMO TM, TA-TRI.
DN 150-200, DN 150-200 HF: TA-Slider 1600.
DN 25-32: TA-Slider 160, TA-TRI, TA-MC50-C*.
DN 40-50: TA-Slider 500, TA-Slider 750*.
DN 65-125: TA-Slider 750.
For more details on actuators, see separate technical leaflets.
TA-Slider 160, 500, 750 and 1600 also available with fail-safe function.
Connection
DN 10-50: External thread according to ISO 228.
DN 65-200: Flanges according to EN-1092-2, type 21. Face to face length according to EN 558, series 1.
Lift
DN 10-20: 4 mm
DN 150: 30 mm
DN 200: 32,5 mm
DN 25-32: 6,5 mm
DN 40-50: 15 mm
DN 65-125: 20 mm
Temperature
DN 10-25 with Δp insert in PPS, DN 40-50: Max. working temperature: 90°C; Min. working temperature: -10°C
DN 10-32: Max. working temperature: 120°C, Min. working temperature: -20°C
DN 40-50: Max. working temperature: 90°C, Min. working temperature: -10°C
DN 65-200: Max. working temperature: 120°C, Min. working temperature: -10°C
Leakage rate
Leakage flow ≤ 0.01% of max. q, max (max. setting) and correct flow direction. (Class IV according to EN 60534-4).
Rangeability
DN 100-150: > 150
DN 100-150 HF: > 125
DN 10-15 LF: > 50
DN 15-32: > 75
DN 200: > 125
DN 200 HF: > 125
DN 40-80: > 125
Characteristics
DN 65-200 HF: Linear
Independent shaped EQM.
Surface treatment
DN 10-50: Non treated
DN 65-200: Electrophoretic painting
Connection to actuator
DN 10-32: M30x1.5, push
DN 40-50: M30x1.5, push/pull
DN 65-200: 2xM8, push/pull
Certifications and directives
DN 65-200: CE, EAC, UKCA
Flow range
DN 10: 17 - 120 l/h
DN 15 LF: 38 - 230 l/h
DN 15: 92 - 480 l/h
DN 20: 200 - 975 l/h
DN 25: 340 - 1750 l/h
DN 32: 720 - 3600 l/h
DN 40: 1000 - 6500 l/h
DN 50: 2150 - 11200 l/h
DN 65: 4150 - 24100 l/h
DN 65 HF: 7460 - 36500 l/h
DN 80: 5850 - 37300 l/h
DN 80 HF: 9520 - 49000 l/h
DN 100: 11700 - 51700 l/h
DN 100 HF: 18000 - 75900 l/h
DN 125: 15000 - 77300 l/h
DN 125 HF: 23300 - 127000 l/h
DN 150: 26100 - 126000 l/h
DN 150 HF: 38800 - 190000 l/h
DN 200: 35000 - 209000 l/h
DN 200 HF: 73200 - 329000 l/h
qmax = l/h at each setting and fully open valve plug.
LF = Low flow
HF = High flow
Art. No. |
---|