TA-Slider 750
Digitally configurable proportional push-pull actuator – 750 N
Digitally configurable actuators for all control systems with or without Bus communication. Wide range of setup possibilities gives high flexibility to adapt parameters on-site. Fully programmable binary input, relay and adjustable max. stroke of the valve bring new opportunities for advanced hydronic control and balancing.
Features and Benefits
Convenient, reliable setup
Fully customisable by smartphone via Bluetooth using a TA-Dongle.
Fully configurable
More than 200 setup options allow input and output signals, binary input, relay, characteristics and many other parameters to be configured.
Easy diagnostics
Tracks the last 10 errors to allow system faults to be found quickly.
Perfection in connectivity
Communication with the most used Bus protocols.
Functions
3-point control
Delayed start-up
Diagnostic/Logging
Error safe position
Manual override
Minimum stroke setting
Mode, status and position indication
On-off control
Output signal VDC
Plus version: With optional BUS communication board. + ModBus or BACnet. With optional relay board. + 1 binary input, max. 100 Ω, cable max. 10 m or shielded. + 2 relays, max. 5A, 30 VDC/250 VAC on resistive load. + Output signal in mA
Proportional control
Stroke detection
Stroke limitation setting
Valve blockage protection
Valve clogging detection
Noise level
Max. 40 dBA
Supply voltage [V]
24 VAC/VDC ±15%., 100-240 VAC ±10%., Frequency 50/60 Hz ±3 Hz
Connection to valve
By two M8 screws to the valve and by quick connection to the stem
Ingress protection
IP54 all directions (according to EN 60529)
Temperature
Media temperature: 0°C – +120°C
Operating environment: 0°C – +50°C (5-95%RH, non-condensing)
Storage environment: -20°C – +70°C (5-95%RH, non-condensing)
Input signal
0(2)-10 VDC, Ri 47 kΩ.
0(4)-20 mA R i 500 Ω.
Adjustable sensitivity 0.1-0.5 VDC; 0.33 Hz low pass filter.
Default setting: Proportional 0-10 VDC
Proportional dual-range (for change-over): 0-3.3 / 6.7-10 VDC, 10-6.7 / 3.3-0 VDC, 2-4.7 / 7.3-10 VDC or 10-7.3 / 4.7-2 VDC.
Proportional: 0-10, 10-0, 2-10 or 10-2 VDC; 0-20, 20-0, 4-20 or 20-4 mA
Proportional split-range: 0-5, 5-0, 5-10 or 10-5 VDC; 0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC; 2-6, 6-2, 6-10 or 10-6 VDC; 0-10, 10-0, 10-20 or 20-10 mA; 4-12, 12-4, 12-20 or 20-12 mA
Control speed
3, 4, 6, 8, 12 or 16 s/mm
Default setting: 3 s/mm
Output signal
0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ.
Default setting: Proportional 0-10 VDC
Plus version: 0(4)-20 mA, max. 700 Ω.
Ranges: See “Input signal”.
Adjusting force
750 N
Protection class
100-240 VAC: Class I.
24 VAC/VDC: Plus version with optional relay board, Class I.
(according to EN 61140)
All other versions, Class III safety extra low voltage.
Stroke
22 mm
Automatic detection of the valve lift (stroke detection)
Certifications and directives
EMC-D. 2014/30/EU: EN 60730-1, -2-14.
LV-D. 2014/35/EU: EN 60730-1, -2-14.
RoHS-D. 2011/65/EU: EN 63000
Cable
Protection class I: H05VV-F or similar
Protection class III: LiYY or similar
*) Note: Wire cross-sections must be chosen according to actuator power consumption and line length, such as the voltage supply to the actuator does not go below 20.4 VAC/VDC (24 VAC/VDC minus 15%).
In case of VDC input signal on a 24 VAC/VDC powered actuator, the voltage drop on neutral line must be smaller than the defined hysteresis level for the VDC input signal
Colour
Orange RAL 2011, grey RAL 7043.,
Marking
LED indication description.,
Material
Cover: PBT
Bracket: Alu EN44200
Power consumption
Operation: 8 VA (VAC); 4.5 W (VDC)
Standby: 1 VA (VAC); 0.5 W (VDC)
100-240 VAC:
Operation: 9.7 VA (VAC)
Standby: 1.8 VA (VAC)
Art. No. |
---|