Skip to main content
TA-Smart – NPT threads/ANSI flanges

TA-Smart – NPT threads/ANSI flanges

2-way control valve with uniquely shaped EQM characteristics with flow, temperature and power measurement capabilities

The ultrasonic flow measurement technology combined with unique actuation algorithms capabilities provide best-in-class control performances. The TA-Smart controls can be set to flow or power, giving high on-site flexibility and providing highly effective comfort in heating and cooling applications. Its compact arrangement and simple set-up reduces installation and commissioning time.

Features and Benefits

Best-in-class control

Accurate and fast control response even at very low flows in common part load conditions. Ensures full modulating control for the complete operating stroke leading to world class control and efficiencies.

Optional cloud connection

Easy remote access to data and configuration parameters allows to verify and adjust system performance.

Optional ΔT and temperature return limitation

Optimize the efficiency of your production units by ensuring optimal temperature regimes.

Change-over functionality

Possibility to switch between two operating conditions to manage seasonality or heating and cooling with the same valve in change-over applications.

High measurement accuracy

High flow and temperature measurement accuracies in all configurations (medium type, and temperature) for all flow regimes.

Compactness and limited number of components

Reduces installation time and space requirements facilitating retrofit installation.

Convenient, reliable setup

Fully customizable and commissionable using Bluetooth enabled smart device reducing commissioning and diagnostic time.

Easy diagnostics

Continuous measurement (flow, temperature, power...) enables accurate error identification in system hydronics.

Versatility in communication

Digital (key Bus protocols and MQTT) and Analog (0(2)-10 VDC or 0(4)-20 mA).

Applications

Heating and cooling systems.

Functions

Control (flow, power, position)

Pre-setting (max./min. flow, max. power, max./min. position)

Reading (flow, power, energy, supply/return temperature, ΔT, position)

Change-over

Delayed start-up

ΔT and temperature return limitation

Diagnostic/Logging

Error safe position

Manual override

Mode, status and position indication

Valve blockage protection

Valve clogging detection

Supply voltage [V]

24 VAC/VDC ±15%. Frequency 50/60 Hz ±3 Hz

Ingress protection

IP54 (according to EN 60529)

Media

Water or neutral fluids, water-glycol mixtures (0-57%).

Temperature

Max. working temperature: 110°C

Min. working temperature: -10°C

Operating environment: 0°C – +50°C (5-95%RH, non-condensing)

Storage environment: -20°C – +70°C (5-95%RH, non-condensing)

Input signal

By BACnet/Modbus or Analog signal. Analog in VDC or mA, selectable by jumper in the SmartBox;

Proportional dual-range (for change-over): 0-4.5 / 5.5-10 VDC. 2-5.5 / 6.5-10 VDC. 0-3.3 / 6.7-10 VDC. 2-4.7 / 7.3-10 VDC. 0-9 / 11-20 mA. 4-11 / 13-20 mA.

0(2)-10 VDC, Ri 47 kΩ.

0(4)-20 mA R i 500 Ω.

Adjustable sensitivity 0.1-0.5 VDC; 0.33 Hz low pass filter.

Default setting: Proportional 0-10 VDC

Proportional: 0-10, 10-0, 2-10 or 10-2 VDC; 0-20, 20-0, 4-20 or 20-4 mA

Proportional split-range: 0-5, 5-0, 5-10 or 10-5 VDC; 0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC; 2-6, 6-2, 6-10 or 10-6 VDC; 0-10, 10-0, 10-20 or 20-10 mA; 4-12, 12-4, 12-20 or 20-12 mA

Leakage rate

DN 15-50: Leakage rate < 0.01% of q, nom with correct flow direction (Class IV according to EN 60534-4)

DN 65-125: Tight sealing with correct flow direction (Class V according to EN 60534-4)

Output signal

0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ.

BACnet/Modbus

Pressure class [PN]

DN 15-50: PN 25

DN 65-125: PN 16, PN 25

Pipe connection

DN 15-50: External thread according to ISO 228. Connections (accessories) with internal thread NPT according to ANSI/ASME B1.20.1-1983, or for soldering according to ASME/ANSI B16.18.

DN 65-125: Flanges according to ASME 7 ANSI B16.42 Class 150.

Protection class

(according to EN 61140)

Surface treatment

DN 15-50: Non treated

DN 65-125: Electrophoretic painting

Flow control accuracy

±10% from 0.5% to 4% of qnom

±5% from 4% to 100% of qnom

Temperature sensor cable

10 m halogen free cable on request.

DN 15-50: 3 m halogen free

DN 65-125: 5 m halogen free

Certifications and directives

EMC-D. 2014/30/EU: EN 60730-1, -2-14.

PED: 2014/68/EU

Product standards EN 60730-x.

Material

Material:
DN 15-50:
Valve body: AMETAL®
Valve insert: AMETAL®
Valve plug: AMETAL® and PTFE
Spindle: Stainless steel
Spindle seal: EPDM O-ring
Internal plastic parts: PPS
Springs: Stainless steel
O-rings: EPDM

Temperature housing: AMETAL®.

DN 65-125:
Valve body: Ductile iron EN-GJS-400-15
Valve insert: Ductile iron EN-GJS-400-15 and brass
Valve plug: Stainless steel and EPDM O-ring
Valve seat: Stainless steel
Spindle: Stainless steel
Spindle seal: EPDM
Springs: Stainless steel
O-rings: EPDM

SmartBox (DN 15-125):
Cover: PC/ABS, red.
Housing: PC/ABS, TPE.

Actuators:
DN 15-50:
Cover: PC/ABS GF8, white RAL 9016, grey RAL 7047.
Housing: PA GF40.
Swivelling nut: Nickel-plated brass.
DN 65-125:
Cover: PBT, orange RAL 2011, grey RAL 7043.
Bracket: Alu EN44200

Flow range

The flow ranges (qsetmin - qnom) for different dimensions:

DN 15: 160 - 1200 l/h
DN 20: 380 - 1900 l/h
DN 25: 540 - 2700 l/h
DN 32: 920 - 4600 l/h
DN 40: 1560 - 7800 l/h
DN 50: 2680 - 13400 l/h
DN 65: 5800 - 29000 l/h
DN 80: 8640 - 43200 l/h
DN 100: 14200 - 71000 l/h
DN 125: 22400 - 112000 l/h

Minimum controllable flows (qcontr.min) DN 15 0.33% of qnom, DN 20-125 0.5% of qnom.

qsetmin = Minimum settable flow.

qnom = Maximum settable flow.

Power consumption

Power consumption:
DN 15-50:
Operation: < 4.0 W (24 VDC); < 5.6 VA (24 VAC)
Standby: < 1.9 W (24 VDC); < 3.3 VA (24 VAC)
DN 65-80:
Operation: < 5.8 W (24 VDC); < 10 VA (24 VAC)
Standby: < 1.9 W (24 VDC); < 3.3 VA (24 VAC)
DN 100-125:
Operation: < 7.7 W (24 VDC); < 10.8 VA (24 VAC)
Standby: < 1.9 W (24 VDC); < 3.3 VA (24 VAC)

Measurement accuracy

Flow:
Water: From 2% accuracy at 100% of qnom to 2.4% accuracy at 5% of qnom (according MID-Class 2 EN1434).
Water+glycol: From 3% accuracy at 100% of qnom to 4% accuracy at 5% of qnom (according to MID-Class 3 EN1434).
(see “Flow accuracy”)
Temperature difference:
±0.1 K @ ΔT = 6 K (for cooling)
±0.15 K @ ΔT = 10 K (for heating)
±0.2 K @ ΔT = 20 K (for heating)

Differential pressure (ΔpV)

Max. differential pressure (ΔpVmax): 400 kPa = 4 bar
Closing pressure: 600 kPa = 6 bar